Siemens: ComDrvS7 Error #509 : Communication error has occurred

Discuss this topic at Factory I/O Community Forum


Some specific Protection & Security settings are required to establish connection between Factory I/O and Siemens S7-1200 or S7-1500 PLCs.

Open the PLC properties, navigate to the Protection & Security section of the General tab and:

  • enable "Permit access with PUT/GET communication from remote partner" under "Connection mechanisms"
  • set protection access level as "HMI access" or higher (Read access or Full access)

You can also refer to a step-by-step guide on how to connect Factory I/O to S7-1200 / S7-1500 PLC.